Manual de utilizare Magnum Standard Control

Magnum Standard Control
9.2 · 1
PDF manual
 · 2 pagini
Engleză
manualMagnum Standard Control

MAGNUM Standard Control

On/O Thermostat

Installation manual

PLEASE READ THIS MANUAL CAREFULLY BEFORE
INSTALLATION, AND STORE WITH OTHER WARRANTEE
FORMS.
The MAGNUM Standard Control is an electronic thermostat
with four functions: Room sensor, oor sensor, power regulator
and room sensor with max./min. limiter. This thermostat can
also be set up for setback temperature.
1. Startup
Remove the adjustment wheel with a screwdriver. The front cover
can the be removed by pushing in the locking clips on each side
of the thermostat (as shown in g.2). Be careful when doing this
in order not to damage the thermostat. When the thermostat has
been connected to the power source, push the on/o button.
Never dismantle the thermostat when the power is switched on.
2. Sensor choice
When choosing a sensor type, the thermostat should not be
connected to a power source.
• Floor sensor (standard)
Jumper placement: Covering the two pins on the left.
Application: The temperature is regulated by the oor sensor.
• Room sensor
Jumper placement: Covering the two pins in the right
Application: The temperature is regulated by the room sensor.
• Room sensor with limiter
Jumper placement: Covering the two pins on the right + the
oor sensor connected
Application: The temperature is regulated by the room sensor,
but the oor sensor overrides the room sensor if the oor
temperature exceeds the maximum limit temperature. The limiter
can be regulated between 20°C and 30°C. For parquet ooring, a
maximum of 27°C is recommended by most ooring manufac-
turers. Please follow the recommendations provided by your
manufacturer.
• Power regulator
Jumper placement: Covering the two center pins
Application: The eect regulator has a 30 min cycle. The desired
on/o interval can be set from 0 to 10, where each level increases
the on-time by 3 minutes.
Example: When the thermostat is set to level 3, the heating
element is switched on for 9 minutes, then o for 21 minutes in
the 30 minute cycle. If the thermostat is set to level 6, the heating
element is switched on for 18 minutes, then o for 12 minutes.
Fig.2
Bi-LED diode
Adjustment wheel
Fig.1
123 4567
HEATING L
SENSOR
PILOT WIRE
L
HEATING N
N
Fig.2
Bi-LED diode
Adjustment wheel
Fig.1
123 4567
HEATING L
SENSOR
PILOT WIRE
L
HEATING N
N
Fig.2
Bi-LED diode
Adjustment wheel
Fig.1
123 4567
HEATING L
SENSOR
PILOT WIRE
L
HEATING N
N
3. Connecting the thermostat
The termostat must be connected to the power source according to
the connection diagram. All heating systems must be equipped with
a residual current disrupter with 30mA. Max load for the thermostat is
16A/3600W at 230V. If the load is higher, the thermostat must be con-
nected to a contactor. The thermostat does not have galvanic insulation
between high and low current. The sensor must therefore be considered
as live (230V) and needs to be installed in accordance with the rules for
high current installations and national installation requirements.
Caution: When reattaching the thermostat cover, make sure the ven-
tilation on the top and bottom of the thermostat is not covered up.
4. Setback temperature
The Multireg thermostat does not have a built-in setback temperature
option, but by connecting an external timer to the S and L clamps, the
temperature can be lowered by 3°C at desired times.
5. Calibrating the temperature
When connecting the oor heating system for the rst time, the tem-
perature should be set at a maximum of 15°C to 20°C. The thermostat
should be calibrated after 2-3 days. Pull out the adjustment wheel
carefully (without turning it) until it comes loose. Use a thermometer to
check the actual temperature, and push the adjustment wheel back onto
the thermometer in accordance with the measured temperature. If the
oor heating has been switched o during the summer, this procedure
should be repeated when it is switched back on.
6. Bi-LED diode
• Green light when the thermostat is in a standby mode.
• Constant red light when the relay is engaged and the power is on.
• Blinking red light when there is a sensor malfunction or the oor sensor
is disconnected.
7. Technical data
Voltage 230 VAC AC ± 15% 50 Hz
Max. load 3600W (resistive load)
Max. current 16 Amp
Power consumption 0,5W
IP-class IP 21
Power regulator Time cycle: 0-30 min
Min/Max inst. temp. -20°C - +60°C
Min/Max oper. temp. 0° - 50°C
Temperature intervals Floor sensor: 5°C - 40°C
Room sensor 5°C - 40°C
Hysteresis 0.5°C
Sensor values 0°C 29,1 Kohm
10°C 18,6 Kohm
15°C 15,1 Kohm
20°C 12,2 Kohm
25°C 10,0 Kohm
Switch 2-pole switch
Colors White RAL 9010 (5430333)
White RAL 9003 (5430444)
Floor sensor Length 3 meters. The cable can be extended
10 meters by using a proper installation cable.
Fig.2
Bi-LED diode
Adjustment wheel
Fig.1

123 4567

HEATING
L
SENSOR
PILO
T WIRE
L
HEATING
N
N
Torque: Max. 2Nm
Clamp 1+ 2Sensor - Floor sensor
Clamp 3: Pilot wire (connected to L for
setback temperature)
Clamp 4: Heating L
Clamp 5: L
Clamp 6: Heating N
Clamp 7: N
Fig.2
Bi-LED diode
Adjustment wheel
Fig.1

123 4567

HEATING L
SENSOR
PILOT WIRE
L
HEATING N
N

Consultați aici manualul pentru Magnum Standard Control, gratuit. Acest manual se încadrează în categoria termostate și a fost evaluat de 1 persoane cu o notă medie de 9.2. Acest manual este disponibil în următoarele limbi: Engleză. Aveți o întrebare despre Magnum Standard Control sau aveți nevoie de ajutor? Puneți întrebarea aici

Aveți nevoie de ajutor?

Aveți o întrebare despre Magnum și răspunsul nu se află în manual? Puneți întrebarea aici. Furnizați o descriere clară și cuprinzătoare a problemei și a întrebării dvs. Cu cât problema și întrebarea dvs. sunt descrise mai bine, cu atât le va fi mai ușor celorlalți proprietari Magnum să vă ofere un răspuns bun.

Ioan Balazs • 18-2-2023Fără comentarii

Ce sa fac an situatia asta

Ce sa fac an situatia asta
Vezi fotografia
Răspundeți la întrebare
Balasz Ioan • 18-2-2023Fără comentarii

Am un Magnum MRC si mia funtionat perfect cam 3 luni dupa aia mia aparut pe ecran esec senzor pardoseala Sincer lam desfacut si mia fost piscat cablul de termostat lam taiat cam 5 cm si lam pus la loc si acum ami arata ca am 45C*Dar acum nu funtioneaza si e rece an camera

Am un Magnum MRC si mia funtionat perfect cam 3 luni dupa aia mia aparut pe ecran  esec senzor pardoseala 
Sincer lam desfac...
Vezi fotografia
Răspundeți la întrebare
Stoian vasile • 13-2-2022Fără comentarii

Când este lucrează termostatul magnum control,când estepornit ledul rosu sau cel verde?

Răspundeți la întrebare

Numărul de întrebări: 3

General
Magnum
Standard Control
termostat
Engleză
Manual de utilizare (PDF)

Nu puteți găsi răspunsul la întrebarea dvs. în manual? Puteți găsi răspunsul la întrebarea dvs. în Întrebările frecvente despre Magnum Standard Control de mai jos.

Unde este cea mai bună locație pentru amplasarea termostatului?

Cel mai bun loc pentru termostat este camera în care petreceți cel mai mult timp, în multe cazuri camera de zi sau bucătăria. Așezați termostatul la aproximativ un metru și jumătate deasupra podelei, nu la soare și nu pe un perete exterior.

Ce este banda moartă a unui termostat?

Dacă termostatul dvs. are o bandă moartă, instalația dvs. este, ca să spunem așa, „în repaus”. Termostatul pornește numai atunci când, de exemplu, diferența se abate mai mult de 2˚C de la temperatura setată a camerei.

Care este temperatura ideală a camerei?

Majoritatea oamenilor consideră că temperatura ideală a camerei este cuprinsă între 19 și 22 de grade Celsius.

Este manualul Magnum Standard Control disponibil în Română ?

Din păcate, nu avem manualul pentru Magnum Standard Control disponibil în Română. Acest manual este disponibil în Engleză .

Întrebarea dvs. nu se regăsește aici? Puneți întrebarea aici

Fără rezultate